Vertiv Liebert ITA2 Double Conversion UPS

In stock
SKU:
ITA2 UPS
$0.00
Vertiv
Brand: Vertiv

Liebert ITA2 Double Conversion UPS offers best-in-class efficiency of up to 96.3% over a wide range of load conditions, resulting in significant OPEX cost savings. ITA2 integrated Smart Sleep technology in ECO mode provides a superlative efficiency of up to 99%.

More Information
Description

In today's dynamic world, it is not enough for enterprises to have basic power protection. With digital trends constantly emerging and transforming the way you do business, business continuity is all the more vital. You simply cannot afford downtime in your critical system or waste time recovering these systems after a disruption. What you need is a robust, high-speed, reliable UPS system, which offers perennial, round-the-clock protection to diverse application needs.

Features
  • Robust structure with cutting edge channelized airflow design
  • Wide input voltage range, making it immune to grid interference
  • Programmable output outlets/ terminals with cascade protection to protect key devices during heavy load
  • Integrated Ethernet port with HTTP protocol compatibility & streamlined remote monitoring
  • Easy to install, repair, and maintain
  • Compliance with seismic conduction & vehicle carrying test
  • Gravity sense LCD Display
    Turnkey Dust-proof design with ability to operate under high ambient temperature of up to 50°c
Specifications
Input Parameters
Nominal Input Voltage (V) 220/230/240VAC 1-Phase, 2 Wire 220/230/240VAC 1-Phase, 2 Wire
380/400/415VAC 3-Phase, 4 Wire 380/400/415VAC 3-Phase, 4 Wire
Input Voltage Range (V) 176-288VAC at full load; 100-176VAC at linear derating; 100VAC at half load 305-477 VAC
Nominal Input Frequency (Hz) 50/60
Input Frequency Range (Hz) 40-70
Input Power Factor (kW/kVA)* 0.99
Current THD at full linear load
Battery
Battery Blocks Per String 12*, 16, 20 24*, 32, 34, 36, 38, 40 32, 34, 36, 38, 40 30*, 32, 34, 36,
38, 40
Battery Charger Max. Power (A) = 5A (Long backup model)
Battery Option P/C : ITA-BCI0020K01 ( built-in battery module of 16 block X 12V X 9AH)
Battery cabinet Dimensions in rack arrangement - 430(W) x 739(D) x 85(H)
Only external
battery cabinet
Output
Nominal Output Voltage (V) 220/230/240 (1-phase) 220/230/240VAC (1-Phase),
380/400/415VAC (3-Phase)
380/400/415VAC
(3-Phase)
Nominal Output Frequency (Hz) 50/60
Rated Power Factor (kW/kVA) Unity 0.9
Voltage Harmonic Distortion (%) <2% for Linear loads & <5% for Non-linear loads
Overload Capacity At 25°C: 105% ~ 125%, 5min; 125% ~ 150%, 1min; 150%, 200ms
Crest Factor 3:1
Efficiency
Online Mode Efficiency Up to 95.5% Up to 95.8% Up to 96.2% Up to 96.5% Up to 95%
ECO Mode Efficiency Up to 99% Up to 98.5%
Dimensions and Weight
Dimensions (W x D x H) in mm
Rack Mounted Arrangement 430x450x85 430x560x85 430x570x130 435x800x173
Weight (kg) 11 15 23 23.5 72
General
Nosie at 1 m (dBA) =55 =58 <60 <58
Operating Temperature (°C) 0 ~ 50* 0 ~ 40
Relative Humidity (%RH) 5 ~ 95, non-condensing
Altitude (m) =3000m ≤1000m
General and safety requirements for
UPS IEC/EN 62040-1
EMC requirements for UPS IEC/EN 62040-2
UPS classification according to
IEC 62040-3 VFI-SS-111