Vertiv Liebert eXM 80kW - 200kW Modular UPS for Data Center
In stock
SKU:
Liebert eXM 80kW
- 24×7 remote and on-site support
- Multi-vendor solutions & services
- Local billing in 33+ countries
- Competitive Price
Small and medium sized businesses need UPS solutions that deliver lower first costs and ongoing operational savings, high reliability, and enable speed and flexibility in a dynamic IT environment. Vertiv’s commitment is to deliver the most technologically advance product for our customer’s mission critical applications, is once again reiterated by our next generation UPS series Liebert eXMTM
- Double Efficiency exceeding 96% at partial load
- ECO mode availability for parallel configurations
- Unity output PF ( kVA=kW)
- Powerful battery charging capability
- Flexible air flow management; from back and top
- Top or bottom cable entry
- Integrated transformer option
- Full frontal access for installation and service
- LIFE™ remote diagnostic and preventive monitoring service
- Robust internal architecture makes it suitable for light industrial application
Input |
Nominal input voltage(V) 380/400/415 |
Input voltage range without |
battery discharge (V) 229-478 |
Nominal input frequency(Hz) 50/60 |
Input frequency range(Hz) 40-70 |
Bypass voltage tolerance(%) Upper limit: +10%, +15%, or +20% default: +15%; |
Lower limit: -10%, -20%, -30% or -40% default: -20% |
Bypass frequency tolerance(%) +/- 10% or +/- 20%, default: +/-10% |
Input power factor(kW/kVA) >0.99 |
Current THD at full linear load(THDi%) <3% |
Battery |
Number 12V battery per string(Min-Max) 30-44 |
Temperature compensation (mV/°C/c1) -3.0 (selectable from 0 to -5.0 around 25°C or 30°C, or inhibit) |
Battery Charger max. (A) 20 24.5 30 40 49 |
Output |
Nominal output voltage (V) 380/400/415 |
Nominal output frequency (Hz) 50/60 |
Nominal active power (kW) PF=1 |
THDv with 100% linear load (%) <1% |
Inverter overload capacity 110% for 60 mirr, 125% 10min; 150% for 1 min |
Efficiency |
Online mode efficiency Up to 96.4% |
ECO mode efficiency Up to 99.1% |
Dimensions and weight |
Dimensions (W x D x H) mm 700 x 1000 x 1500 900 x 1000 x 2000 900 x 1000 x 2000 1200 x 1000 x 1700 1200 x 1000 x 1700 |
Weight(Net weight) 350 480 480 580 625 |
General |
Nosie at 1 m dB(A) 57 59 59 61 64 |
Altitude =1500; derate power by 1% per 100m between 1500m and 300m |
Ventilation Front to back standard/ Front to top (optional) |
Protection level IEC (60629) IP 20 Standard |
General and safety requirements for UPS EN62040-1/ IEC62040-1 /A562040-1 |
EMC requirements for UPS EN62040-2 / IEC62040-2 / AS62040-2 (Class C2*) |
Method of specifying the performance |
and test requirements of UPS EN62040-3 / IEC62040-3 / AS62040-3 (VFI-SS-111) |