Anord Mardix Databar Busway
In stock
SKU:
Databar
- 24×7 remote and on-site support
- Multi-vendor solutions & services
- Local billing in 33+ countries
- Competitive Price
ENGINEERED FOR OPTIMUM SAFETY AND EFFICIENCY
The unique tap-off design also provides the essential safety element when inserting a tap-off onto a live busway system. The power contacts are engaged via a patented actuation system that not only controls the tap-off contacts but also interlocks with the switching device to ensure that no load is connected during the engaging operation.
INDUSTRY LEADING BENEFITS
- The compact design of the DATABAR busway is ideal in situations where low ceiling height and IT / fiber conduits compete for space.
- Safety in simplicity and scalability – there are only two DATABAR sizes: 160a-630a and 800a-1000a. The same low-profile housing accommodates both 4 and 5-pole systems while maintaining the smallest footprint design.
- The open channel modular busway construction allows the tap-off units to be placed at any location along the busway. Tap-off designs are available to install over the joint if necessary and the whole design is aimed at flexibility and simplicity.
- Easy installation, extension and development means that an investment in DATABAR today will still be giving you a return in years to come
- Independently certified by ASTA to BS EN / IEC 61439-6
- Two busway designs; DX for 160A to 630A and DX Plus for 800 to 1000A systems with 3, 4 or 5 poles in the same footprint
- Continuous open channel permits tap-offs to be installed anywhere along the busway (IP2X)
- Flexible extension and re-configuration with integral plug-n-play jointing system
- A patented design feature within the tap-off unit centres around the actuator mechanism puts safety and efficiency at the forefront of the design and installation process.
- IP3X achievable by using the channel cover strip solution
- Available in 1m, 2m and 3m lengths as standard. Non -standard lengths also available on request
- Optional overrated neutrals or 100% integral earth conductor
- The busbar trunking system has also been independently tested for resistance to Arc Flash in accordance with IEC / BS EN 61641 and seismically tested to IEEE 344-2103.
Rated Current | In [A] | 160, 250A, 400A, 630A |
Rated operating voltage | Ue [V] | 600 |
Rated insulation voltage | Ui [V] | 1000 |
Frequency | f[Hz] | 50/60 |
Degree of protection | IP | 2X |
Casing Material | Aluminium | |
Conductor material | Cu (99.9%) BS EN 13601 | |
Case dimensions (4 or 5 pole systems) | W x H mm | 165 x 47 |
Phase Neutral or Isolated Earth Conductor CSA | CSA [mm2] | 1457 |
Case Earth (PE) CSA | CSA [mm2] | 194 |
Weight (4 pole systems) | p[kg/m] | 12.9 |
Weight (5 pole systems) | p[kg/m] | 14.5 |
Rated short-time current for three phase fault | Icw[kA] rms | 30 |
Allowable peak current for three phase fault | Ipk [kA] | 64.2 |
Rated conditional protection for three phase fault | Icc [kA] | 50 |
Conditional protection peak current rating | Ipk [kA] | 106 |
Impact Resistance | IK | IK08 |