Server Technology Switched POPS PDU - 8.6kW, C2WG24SN-DCLN5D6
- 24×7 remote and on-site support
- Multi-vendor solutions & services
- Local billing in 33+ countries
- Competitive Price
The Server Technology® PRO2 Switched POPS PDU provides control of outlet power and local LED input current monitoring, allowing IT personnel to determine safe levels of loading on a per-phase basis while installing equipment into the rack/cabinet. The integral PIPS® and POPS® technology provides billing-grade accurate measurement of current, voltage, active power, apparent power, power factor, crest factor, and accumulated energy at the input and at each output. These power data points, along with temperature and humidity measurements (provided via optional probes), are accessible through the built-in Web and CLI interfaces as well as through SNMP. The PRO2 Switched POPS “Primary” PDU can be connected to as many as three (with optional module) PRO2 Switched POPS “Link” PDUs to extend the network access to the redundant or secondary power feed without the risks of a daisy chain linking configuration.
Inputs
Input Voltage (V): | 208 |
Input Plug: | NEMA L15-30P |
Input Current (A): | 30 |
Input Current Rated (A): | 24 |
Input Power Capacity (kW): | 8.6 |
Outputs
Connector | Rating |
(18) x IEC 60320/C13 | North American Rating: ≤ 12A @208V L-L (15A Peak) |
(6) x Cx | North American Rating: ≤ 16A @208V L-L (20A Peak) |
Branch Circuit Protection - UL489 Compliant 2-pole, 20A trip circuit breakers, three (3) branch, rating: ≤ 16A, 10 kAIC (North America) / (5 kAIC ROW) Interrupt Rating
Physical -Dimensions: 3.5in tall x 17.2in wide x 17.5in deep [89mm x 437mm x 445mm]
Environmental
Operating Environment:32°F to 140°F / 0°C to 60°CStorage Environment:40°F to 185°F / -40°C to 85°C